Chillers larger than about 100 tons usually have water
circulating through the condenser. This water removes the heat from the
chiller (the contribution due to the cooling as well as removing the heat
from the motor, engine or absorber). Therefore a high efficiency electric
chiller rated at 0.6 kW per ton rejects approximately 14,000 Btuh/ton of
cooling. A high efficiency absorption chiller with a COP of 1.0 rejects
about 24,000 Btuh/ton of cooling.
The circulating cooling tower water flow is determined primarily by the
range in temperature. For example, with a high efficiency electric chiller,
a 10°F range (e.g., supplying 85°F water to the chiller condenser and
heating that water to 95°F), requires a condenser water flow of about 2.8
gpm per ton. With the same 10°F range, it would have to be about 4.8 gpm per
ton for the high efficiency absorption chiller. This flow can be reduced by
widening the range, but that would decrease the efficiency of the chiller
itself.
The temperature of the water sent to the chiller condenser from the
cooling tower is determined, largely by the ambient wet bulb temperature and
the efficiency of the cooling tower (the amount of air drawn through the
tower and the efficiency of air-water contact). Dry bulb temperature has
only a minimal impact on cooling tower performance. The cooling tower is
normally specified to meet the design wet bulb temperature in any geographic
area -- commonly 75° to 78°F. The cooling tower manufacturer then designs
the tower to produce 85°F water under this condition for the design heat
rejection level and water flow. The temperature difference between the water
sent to the condenser (i.e. coming off the cooling tower) and this wet bulb
figure (say 78°F) is defined as the approach temperature 7°F (= 85 - 78).
This design day wet bulb condition occurs relatively few hours a year in
most parts of the United States. During dryer times, the cooling tower can
produce colder water than 85°F. And, most chillers will operate with reduced
power input if this water temperature is reduced (down to a given limit as
specified by the equipment manufacturer). This concept is called "floating
the condenser" and holds the potential of conserving energy and reducing
operating costs.
Selecting the condenser water parameters and cooling tower design is very
complicated. Design of these systems requires experience, careful analysis,
and consideration of initial investment and operating costs. The material
presented here is simply an explanation of several design parameter
opportunities. Please refer to the specific cooling design modules elsewhere
in this information system for additional details.
Formula: Btuh = gpm x range in °F x 500
where: 500 = 60min/hr x 8.33 lb/gal of water
|